EVP 400/C – 60Hz

EVP 400/C – 60Hz


Project Description

Minimum operating temperature - 20 ° C, Maximum + 60 ° C.

ATEX mode is not suitable for this fan category for structural reasons.

ErP : These fans are within the scope of Directive 2009/125 / EC. This law does not apply in the following cases:
- Operation in potentially explosive atmospheres (ATEX)
- Operation at high temperatures (fans designed with cooling fan)
- Operation at temperatures below -40°C

- Working in toxic, corrosive or corrosive environments (use of materials such as AISI 304, AISI 316, manganese steels).
These series are axial fans and therefore Ntarget = 50 is expected (Reg. UE N.327 / 2011).
Efficiency IE2 motors conforming to IEC 60034-30 are taken into account in ErP calculations.

HAVA AKIMI

V = 1.320 ÷ 8.500 M3/SAAT

BASINÇ

PT =  4 ÷ 45 KG/M2

Product Technical Information

AIR FLOW 95 – 150 m3/minute
INPUT PRESSURE 25.799999 – 60 kg/m2
OUTPUT PRESSURE 28 – 60.5 kg/m2
ENGINE BOARD 90 L – 2 poles
INSTALLED POWER 2.2 kW
ROTATION SPEED 3400 rpm
SPEED LIMIT 3450 rpm
LIQUID TYPE Clean
INLET FLANGE ⌀400mm
OUTLET FLANGE 400 x N/A mm
WEIGHT WITHOUT MOTOR 19 Kg
SE 2 N/A Kgm2

Use : Helical fans, EVP series are suitable for suction of fumes and dirty, dusty and wet air in foundries, cement factories, paper mills and woodworking works.
For ventilation of local rooms, radiator, unit heaters, cooling towers, etc. It is used in applications for drying paper, wool, pasta tiles and generally where large volumes of air must be conveyed at low pressure.

– Easy setup

– High energy saving

– Silent

– Made with high quality raw materials

– Long years of use guarantee