Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the really-simple-ssl domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version in /home/euroofa/public_html/wp-includes/functions.php on line 6114
EVF 1120/F – Euroofan

EVF 1120/F

EVF 1120/F


Project Description

Minimum operating temperature - 20 ° C, maximum + 70 ° C.

ErP : These fans are within the scope of Directive 2009/125 / EC. This law does not apply in the following cases:
- Operation in potentially explosive atmospheres (ATEX)
- Operation at high temperatures (fans designed with cooling fan)
- Operation at temperatures below -40 °C
- Working in toxic, corrosive or corrosive environments (use of materials such as AISI 304, AISI 316, manganese steels).
These series are axial fans and therefore Ntarget = 50 is expected (Reg. UE N.327 / 2011).
Efficiency IE2 motors conforming to IEC 60034-30 are taken into account in ErP calculations.

HAVA AKIMI

V = 1.320 ÷ 120.000 M3/SAAT

BASINÇ

PT = 4 ÷ 100 KG/M2

Product Technical Information

AIR FLOW 1240 – 1470 m3/minute
INPUT PRESSURE 40 – 70 kg/m2
OUTPUT PRESSURE 40 – 70 kg/m2
ENGINE BOARD 180 M – 4 poles
INSTALLED POWER 18.5 kW
ROTATION SPEED 1450 rpm
SPEED LIMIT 1500rpm
LIQUID TYPE Clean
INLET FLANGE ⌀1120mm
OUTLET FLANGE 1120 x N/A mm
WEIGHT WITHOUT MOTOR 235 Kg
SE 2 N/A Kgm2

Use : Helical fans, EVF series, are suitable for suction of dirty, dusty and wet air as well as fumes in foundries, cement plants, paper mills and woodwork.
For ventilation of local rooms, radiator, unit heaters, cooling towers, etc. In applications for drying paper, wool, pasta tiles and generally where large volumes of air must be conveyed at low pressure.

– Easy setup

– High energy saving

– Silent

– Made with high quality raw materials

– Long years of use guarantee