EVL 1250/A

EVL 1250/A


Project Description

Minimum operating temperature - 20 ° C, Maximum + 60 ° C.

ErP : These fans are within the scope of Directive 2009/125 / EC. This law does not apply in the following cases:
- Operation in potentially explosive atmospheres (ATEX)
- Operation at high temperatures (designed fans with cooling fans)
- Operation at temperatures below -40 °C
- Working in toxic, corrosive or corrosive environments (use of materials such as AISI 304, AISI 316, manganese steels).
These series are axial fans and therefore Ntarget = 50 is expected (Reg. UE N.327 / 2011).
Efficiency IE2 motors conforming to IEC 60034-30 are taken into account in ErP calculations.

HAVA AKIMI

V = 1.320 ÷ 120.000 M3/SAAT

BASINÇ

PT = 4 ÷ 100 KG/M2

Product Technical Information

AIR FLOW 765 – 1080 m3/min
INPUT PRESSURE 14 – 30 kg/m2
OUTPUT PRESSURE 14 – 30 kg/m2
ENGINE BOARD 160 M – 8 poles
INSTALLED POWER 5.5 kW
ROTATION SPEED 720rpm
SPEED LIMIT 770 rpm
LIQUID TYPE Clean
INLET FLANGE ⌀1250mm
OUTLET FLANGE 1250 x N/A mm
WEIGHT WITHOUT MOTOR 280 Kg
SE 2 N/A Kgm2

Use : EVL series helical fans are suitable for suction of dirty, dusty and wet air as well as fumes in foundries, cement plants, paper mills and joinery works.
Used in the ventilation of local rooms, radiators, unit heaters, cooling towers, etc. In applications, drying paper, wool, pasta tiles and generally where it is necessary to convey large volumes of air at low pressure.

– Easy setup

– High energy saving

– Silent

– Made with high quality raw materials

– Long years of use guarantee