BPR 901/C

BPR 901/C


Project Description

The temperature of the transported fluid should not exceed 80 °C without cooling fan and 150 °C with cooling fan. For higher temperatures, it is necessary to change the structure of the fan.

ErP : These fans are within the scope of Directive 2009/125 / EC. This law does not apply in the following cases:

- Operation in potentially explosive atmospheres (ATEX)

- Operation at high temperatures (fans designed with cooling fan)

- Operation at temperatures below -40 °C

- Working in toxic, corrosive or corrosive environments (use of materials such as AISI 304, AISI 316, manganese steels).
These series are centrifugal backward curved fans and therefore Ntarget = 61 is expected (Reg. UE N.327 / 2011).
Efficiency IE2 motors conforming to IEC 60034-30 are taken into account in ErP calculations.

HAVA AKIMI

V = 1.320 ÷ 96.000 M3/SAAT

BASINÇ

PT= 10 ÷ 390 KG/M2

Product Technical Information

AIR FLOW 355 – 1120 m3/minute
INPUT PRESSURE 109 – 291 kg/m2
OUTPUT PRESSURE 110 – 300 kg/m2
ENGINE BOARD 225 M – 4-pole
INSTALLED POWER 45 kW
ROTATION SPEED 1475 rpm
SPEED LIMIT 1525 rpm
LIQUID TYPE Clean
INLET FLANGE ⌀908mm
OUTLET FLANGE 900x630mm
WEIGHT WITHOUT MOTOR 429 Kg
SE 2 38 Kgm2

Use : To remove clean or slightly dusty air. They have high efficiency and low noise level, the fans of this series are mainly used in the following industries, ventilation, air-conditioning, drying, cooling, mechanical airflow and toxic gas removal plants.

– High energy saving

– Silent

– Made with high quality raw materials

-Long years of use guarantee

-Easy setup